Welcome to visitWuhan Xinshengneng Technology Co., Ltd.
Your location:Home > News > Industry dynamic
Industry dynamic

Precautions for test preparation and use of Xinshengneng Zinc oxide arrester tester

AddTime:2021-11-05 16:42:37   Views:     【 Big Mid Small 】   Print   Close

Zinc oxide arrester tester is used to test the electrical performance of zinc oxide arrester special instrument, the instrument is suitable for all kinds of voltage levels of zinc oxide arrester live or power failure detection, so as to timely find the equipment internal insulation moisture and valve aging and other dangerous defects.

Preparation and attention to use of zinc oxide arrester tester before test

1. First check whether the surface of the zinc oxide arrester tester is dry and clean, and whether the power cord, connecting cable and grounding wire are intact.

2. After connecting the grounding end of the measurement and control box with the grounding end of the high voltage box, the grounding wire from the grounding end of the high voltage box is firmly connected to the ground network, and the wire is led out. At the same time, ensure that there is enough safety distance between the measuring and controlling box and the high pressure box.

3. Connect the measuring and controlling box with the connecting cable.

4, the lower end of the test (insulation to the ground) access to the high pressure box "test" end, the upper end access to the high pressure box high pressure end.

5, the high voltage lead must be used with insulated wire, in order to reduce the high voltage lead to the ground corona current, and pay attention to the ground insulation.

6, the test is completed, be sure to adjust the zinc oxide arrester tester coarse button complex zero, turn off the high pressure, wait for the green light, the grounding wire hanging in the high pressure end, finally can contact the high pressure end or replace the test.

Precautions for zinc oxide arrester tester:

1. When taking the reference voltage from PT or the measuring end of the test transformer, the wiring should be carefully checked to avoid the short circuit of PT secondary or test voltage.

2, if the LCD character display becomes light due to climate change and other reasons, the contrast can be adjusted properly to adjust the rotating button, so that the character is clear.

3. If there is abnormal damage to the zinc oxide arrester tester, please stop using it immediately and notify the after-sales service. Do not open the box for repair.

Wuhan Xinshengneng Technology Co., Ltd. is a lightning arrester testing equipment manufacturer, the production of a variety of products, complete models, to provide professional technical support, tel 0312-3188565.


Prev:Xinshengneng expounds the short circuit test method of grounding resistance tester  Next:Wuhan Xinshengneng describes the advantages of transformer short circuit impedance tester


Back To Top

Qr code scan

Copyright © Wuhan Xinshengneng Technology Co., Ltd. All Rights Reserved  鄂ICP备2020019985号-1   Web site productionsanjin.net