In the series resonance experiment, the automatic tuning of the device cannot be completed and the reason of the resonance point cannot be found

AddTime:2021-09-09 08:43:04   Views:     【 Big Mid Small 】   Print   Close

Phenomenon:

The tuning curve is a straight line, and the instrument indicates no resonance point after tuning

The reason:

Circuit grounding is not good, the wiring of the test circuit is wrong, the device of an instrument open

Elimination method:

1) Check whether the grounding device is reliable and the grounding connecting wire is disconnected;

2) Check the on and off of the high and low voltage coils of the excitation transformer; (Low voltage winding resistance; High voltage winding resistance per output end vs high voltage tail)

3) Check the on-off of each reactor; (Resistance of each winding)

4) Check the on-off of the signal line of the voltage divider; (High and low voltage capacity)

5) Check the on and off of the high-low voltage capacitor arm of the voltage divider; (1 hole on the core, 2 holes on the shell respectively; 1 hole to 2 hole disconnect)

6) There is no resonance point in the boost of the device itself, so it is necessary to check the on-off of the compensation capacitor;

If all parts are normal and there is still no resonance point, please contact Wuhan Xinshengneng Technology Co., LTD., do not disassemble the instrument!