Welcome to visitWuhan Xinshengneng Technology Co., Ltd.
  • Withstand voltage test equipment

  • High voltage test equipment such as transformers and switches

  • Oil and gasification test equipment

  • Relay protection and secondary circuit test equipment

  • Live and online monitoring equipment

  • Electricity inspection power metering equipment

  • Insulation tool test equipment and battery

  • Others

  • High voltage integrated equipment series

  • SF6 gas test equipment series

  • Insulating appliance series

  • Marketing measurement test equipment series

  • Series resonance

    110kV transformer without partial discharge series resonance

    Views:

    ●Product introduction

    Product name: 110kV transformer without partial discharge series resonance
    Product specifications: XSN (XZ)-100kW without partial discharge frequency conversion power supply
    Applicable test product: Transformer
    Test product range: As a power transformer with a voltage level of 110kV and below, the capacity is not more than 120MVA, the power system for partial discharge and induction withstand voltage test

    Product function and function: ①Help customers to achieve preventive AC withstand voltage test and handover AC withstand voltage test of various tested products; ②Test cross-linked rubber and plastic power cables, power transformers, GIS, transformers, insulators, generators AC withstand voltage test of insulation withstand various overvoltages and capacitive loads of the tested product such as switches.

    Product nicknames: series resonance withstand voltage test equipment, AC withstand voltage test equipment, inspection resonant booster device, series resonance withstand voltage tester

    Test object: As a power transformer with a voltage level of 110kV and below, the capacity is not greater than 120MVA, and the power supply system for partial discharge and induction withstand voltage tests. The low-voltage side voltage of the tested product is designed according to the specifications of 35kV and below.

    ●Technical parameters

    No partial discharge resonance console:
    Model: CZT(W)-100;
    Power supply voltage and frequency: three-phase 380V±15%; 50Hz (the partial discharge interference level of the power supply is less than 20pC);
    Power supply capacity: more than 120kVA
    Rated output power: 100kW (maximum output active power);
    Rated output voltage: 0~350V, continuously adjustable;
    Rated output current: 286A;
    Output phase number: single phase;
    Output waveform: pure sine wave;
    Output waveform distortion rate: ≤1.0%;
    Output voltage instability: ≤1.0%;
    Cooling method: forced air cooling;
    Adjustable frequency range: 20Hz~300Hz;
    Output frequency resolution: 0.1Hz;
    Output frequency instability: ≤0.5%;
    Noise level: ≤80dB;
    Partial discharge capacity: <5pC;
    Allowable running time: Allowable running time under rated capacity ≥ 1 hour;
    Allowable temperature rise: under rated load, continuous work for 180min, temperature rise of air outlet ≤45K;

    Without partial discharge excitation transformer:
    Model: JLB(W)-100;
    Rated capacity: 100kVA;
    Number of phases: single phase
    Low-voltage winding phase voltage: 2×350V; 2×400V; 2×450V;
    Low-voltage rated current: 286A;
    Rated voltage of high-voltage winding: 2×10kV; 2×35kV; (The high-voltage winding is composed of two independent windings. When connected in parallel, the partial discharge test of the low-voltage side of 6.3kV transformer can be carried out; when connected in series, the partial discharge test of low-voltage side is 10kV/35kV transformer .)
    Insulation level: induced voltage 1.2 times 1min;
    Rated frequency: 50~300Hz;
    Partial discharge capacity: Partial discharge capacity under rated voltage ≤10pC;
    Impedance voltage: ≤5%;
    Noise level: ≤65dB;
    Rated temperature rise: winding temperature rise is less than 65K;
    Allowable continuous operation time: 60min continuous operation under rated voltage and rated current;

    Compensating reactor without partial discharge:
    Model: DK(W)-140/35
    Rated voltage: 35kV;
    Rated current: 4A/60min
    Inductance value: 14H;
    Rated capacity: 140kVA;
    Frequency of use: 100~300Hz;
    Non-linearity of inductance value: ≤1%;
    Insulation level: The reactor should be able to withstand a working voltage 1.2 times its rated voltage without flashover or breakdown for 1 min;
    Partial discharge capacity at rated voltage: <10pC;
    Allowed continuous operation time: 60min continuous operation under rated voltage and rated current;

    Without partial discharge divider:
    Model: FY (W)-500/100;
    Rated voltage: 100kV;
    Electric capacity: C1=500pF;
    Working frequency: 30~300Hz;
    System measurement error: ≤2.0%;
    Insulation level: 110kV/1min;
    Dielectric loss: ≤0.2%;
    Structure: C1 is a capacitor with epoxy cylinder shell and oil-paper insulation structure;
    C2 selects materials with the same temperature coefficient and frequency coefficient as C1.
    Partial discharge capacity: ≤10pC;

    Back To Top
    Copyright © Wuhan Xinshengneng Technology Co., Ltd. All Rights Reserved  鄂ICP备2020019985号-1   Web site productionsanjin.net