Welcome to visitWuhan Xinshengneng Technology Co., Ltd.
  • Withstand voltage test equipment

  • High voltage test equipment such as transformers and switches

  • Oil and gasification test equipment

  • Relay protection and secondary circuit test equipment

  • Live and online monitoring equipment

  • Electricity inspection power metering equipment

  • Insulation tool test equipment and battery

  • Others

  • High voltage integrated equipment series

  • SF6 gas test equipment series

  • Insulating appliance series

  • Marketing measurement test equipment series

  • Series resonance

    220kV series resonance AC withstand voltage device

    Views:

    ●Product introduction
    Product name: 220kV series resonance AC withstand voltage device
    Product specifications: XSN (XZ) -400kVA/400kV
    Applicable test products: cables, main transformers, switches,
    Test product range: 220kV/80MVA main transformer neutral point, 220kV and below voltage level switch, 35kV/240mm2 cable 1km, 110kV/300mm2 cable 0.2km, 220kV/300mm2 cable 0.08km

    ●Product role and function:

    1. Help customers to achieve preventive AC withstand voltage test and handover AC withstand voltage test of various tested products;
    2. Test cross-linked rubber-plastic power cables, power transformers, GIS, transformers, insulators, generators, switches and other test products insulation withstand various overvoltage capabilities and AC withstand voltage test for capacitive loads.

    Product nicknames: series resonance withstand voltage test equipment, AC withstand voltage test equipment, inspection resonant booster device, series resonance withstand voltage tester.

    Test object: 1. AC withstand voltage test of 220kV and below voltage switch, test frequency 30-300Hz, test voltage not exceeding 395kV, test time 1min.
    2. AC withstand voltage test at the neutral point of 220kV/80MVA main transformer, capacitance ≤0.02uF, test frequency 45-65Hz, test voltage 160kV, test time 1min.
    3. AC withstand voltage test of 1km of 35kV/240mm2 cable, electric capacity ≤0.1805uF, test frequency 30-300Hz, test voltage 52kV, test time 60min.
    4. AC withstand voltage test of 110kV/300mm2 cable 0.2km, capacitance ≤0.0294uF, test frequency 30-300Hz, test voltage 128kV, test time 60min.
    5. AC withstand voltage test of 220kV/300mm2 cable 0.08km, capacitance ≤0.0094uF, test frequency 30-300Hz, test voltage 216kV, test time 60min

    ●Technical parameters
    1. Rated capacity: 400kVA;
         Input power: three-phase 380V voltage, frequency 50Hz;
         Rated voltage: 200kV; 400kV
         Rated current: 2A; 1A
         Working frequency: 30-300Hz;
         Device output waveform: sine wave
         Waveform distortion rate: output voltage waveform distortion rate ≤ 1%;
         Working time: allow continuous 60min under rated load; overvoltage 1.1 times 1 minute;
         Temperature rise: the temperature rise after 60 minutes of continuous operation under rated load is           ≤65K;
         Quality factor: the device itself Q≥30 (f=45Hz);
         Protection function: overcurrent, overvoltage and flashover protection for the tested product (see the           frequency conversion power supply section for details);
         Measurement accuracy: system effective value 1.5;

    2. Excitation transformer JLB-22kVA/5/10/20kV/0.4kV 1 set
         Rated capacity: 22kVA;
         Input voltage: 0-400V, single phase;
         Output voltage: 5/10/20kV
         Structure: dry type;
         Weight: about 120kg;

    3. Frequency conversion power supply BP-22kW/220/380V 1 unit
         Rated output capacity: 22kW
         Power supply: 220/380±10%V (single/three-phase), power frequency
         Output voltage: 0 -400V, single phase,
         Rated input current: 55A
         Rated output current: 55A
         Voltage resolution: 0.01kV
         Voltage measurement accuracy: 1.5%
         Frequency adjustment range: 30 – 300Hz
         Frequency adjustment resolution: ≤0.1Hz
         Frequency stability: 0.1%
         Running time: continuous 60min under rated capacity
         The maximum temperature of the components during continuous operation for 60min under the rated           capacity is ≤65K;
         Noise level: ≤50dB;

    4. High-voltage reactor DK-50kVA/50kV 8 sections
         Rated capacity: 50kVA;
         Rated voltage: 50kV;
         Rated current: 1A;
         Inductance: 90H/single section;
         Quality factor: Q≥30 (f=45Hz);
         Structure: dry type;
         Weight: about 60kg;

    5. Capacitive voltage divider FY-400kV/400pF 1 set
         Rated voltage: 400kV;
         High voltage capacity: 400pF
         Dielectric loss: tgσ≤0.5%;
         Partial pressure ratio: 5000:1
         Measurement accuracy: effective value 1.5;
         Weight: about 40kg;

    Back To Top