Welcome to visitWuhan Xinshengneng Technology Co., Ltd.
  • Withstand voltage test equipment

  • High voltage test equipment such as transformers and switches

  • Oil and gasification test equipment

  • Relay protection and secondary circuit test equipment

  • Live and online monitoring equipment

  • Electricity inspection power metering equipment

  • Insulation tool test equipment and battery

  • Others

  • High voltage integrated equipment series

  • SF6 gas test equipment series

  • Insulating appliance series

  • Marketing measurement test equipment series

  • Series resonance

    110kV series resonance AC withstand voltage device

    Views:

    ●Product introduction
    Product name: 110kV series resonance AC withstand voltage device
    Product specifications: XSN (XZ) -540kVA/270kV
    Applicable test products: cables, main transformers, switches, GIS
    Test product range: 110kV switch, GIS, 110kV/63MVA main transformer fully insulated, 110kV/630mm² length 0.6km, 35kV/300mm² length 2.5km, 10kV/300mm² length 5km

    ●Product role and function:

    1. Help customers to achieve preventive AC withstand voltage test and handover AC withstand voltage test of various tested products;
    2. Test cross-linked rubber-plastic power cables, power transformers, GIS, transformers, insulators, generators, switches and other test products insulation withstand various overvoltage capabilities and AC withstand voltage test for capacitive loads.

    Product nicknames: series resonance withstand voltage test equipment, AC withstand voltage test equipment, resonant booster device for inspection, series resonance withstand voltage tester.

    Test object: AC withstand voltage test of 110kV/630mm² cable with a length of 0.6km, capacitance ≤0.121uF, test frequency 30-300Hz, test voltage 128kV, test time 60min.
    AC withstand voltage test of 35kV/300mm² cable with a length of 2.5km, capacitance ≤0.486uF, test frequency 30-300Hz, test voltage 52kV, test time 60min.
    AC withstand voltage test of 10kV/300mm² cable with a length of 5km, capacitance ≤1.88uF, test frequency 30-300Hz, test voltage 22kV, test time 5min.
    AC withstand voltage test of 110kV/63MVA main transformer full insulation, capacitance ≤0.02uF, test frequency 45-65Hz, test voltage not exceeding 160kV, test time 1min.
    AC withstand voltage test of 110kV switch and GIS, the test frequency is 30-300Hz, the test voltage does not exceed 265kV, and the test time is 1min.

    ●Technical parameters
    1. Product core parameters
         Rated capacity: 540kVA;
         Input power: three-phase 380V voltage, frequency 50Hz;
         Rated voltage: 270kV; 135kV; 90kV;
         Rated current: 2A; 4A; 6A;
         Working frequency: 30-300Hz;
         Device output waveform: sine wave
         Waveform distortion rate: output voltage waveform distortion rate ≤ 1%;
         Working time: allow continuous 60min under rated load; overvoltage 1.1 times 1 minute;
         Temperature rise: the temperature rise after 60 minutes of continuous operation under rated load is           ≤65K;
         Quality factor: the device itself Q≥30 (f=45Hz);
         Protection function: overcurrent, overvoltage and flashover protection for the tested product (see the           frequency conversion power supply section for details);
         Measurement accuracy: system effective value 1.5;

    2. Excitation transformer JLB-30kVA/4/8/16kV/0.4kV 1 set
         Rated capacity: 30kVA;
         Input voltage: 0-400V, single phase;
         Output voltage: 4/8/16kV
         Structure: dry type;
         Weight: about 120kg

    3. Inverter power supply BP-30kW/220/380V 1 unit
         Rated output capacity: 30kW
         Working power supply: 220/380±10%V (single/three-phase), power frequency
         Output voltage: 0-400V, single phase,
         Rated input current: 75A
         Rated output current: 75A
         Voltage resolution: 0.01kV
         Voltage measurement accuracy: 1.5%
         Frequency adjustment range: 30 – 300Hz
         Frequency adjustment resolution: ≤0.1Hz
         Frequency stability: 0.1%
         Running time: continuous 60min under rated capacity
         The maximum temperature of the components during continuous operation for 60min under the rated           capacity is ≤65K;
         Noise level: ≤50dB

    4. High-voltage reactor DK(G)-90kVA/45kV Section 6
         Rated capacity: 90kVA;
         Rated voltage: 45kV;
         Rated current: 2A;
         Inductance: 80H/single cell;
         Quality factor: Q≥30 (f=45Hz);
         Structure: dry type;
         Weight: about 90kg;

    5. Capacitor voltage divider FY-270kV/1000pF 1 set
         Rated voltage: 270kV;
         High voltage capacity: 1000pF
         Dielectric loss: tgσ≤0.5%;
         Partial pressure ratio: 3000:1
         Measurement accuracy: effective value 1.5;
         Weight: about 26kg

    Back To Top