●Product introduction
Product name: Regulated inductive non-partial discharge reactor
Product specifications: XSN (DK) -400kVA/400kV
Applicable test product: Transformer
Test product range: 220kV 500kV transformer
●Product function and function:
①Help customers to achieve preventive AC withstand voltage test and handover AC withstand voltage test of various tested products;
②Test cross-linked rubber and plastic power cables, power transformers, GIS, transformers, insulators, generators AC withstand voltage test of insulation withstand various overvoltages and capacitive loads of the tested product such as switches.
Product nicknames: series resonance withstand voltage test equipment, AC withstand voltage test equipment, resonant booster device for inspection, series resonance withstand voltage tester, AC withstand voltage test of 220kV, 500kV transformers and other substation equipment, test frequency 30- 300Hz, test voltage does not exceed 95kV, test time 1min.
●Technical parameters
Adjustable reactor without partial discharge:
No local discharge reactor DK(W)-400kVA/400kV 1 set
Rated capacity: 400kVA;
Rated voltage: 400kV;
Rated current: 1A;
Adjustable inductance range: 500-2500H;
Quality factor: Q≥50;
Working time: 60 minutes;
Structure: inflatable;
Weight: about 800kg;
Partial discharge: ≤10pc
Ruler inch: Φ600*2000mm