Product specifications: XSN-JF-03
Xsn-jf-03 High frequency partial discharge inspection instrument for live inspection characteristics, using high frequency current and ultrasonic two detection methods, its small volume, excellent performance, easy to operate. Can be cable, transformer (reactor) grounding line measurement. The system adopts modern electronic and computer integrated technology to realize signal amplification (analog, electronic, digital), filtering, data acquisition, data processing, graphic display, automatic generation of test report, so as to complete partial discharge measurement and analysis.
Product name: partial discharge detector, ultrasonic partial discharge detector, partial discharge tester, local discharge detector, local discharge detector.
Test subjects:
The ultrasonic signal is received to judge the existence and position of partial discharge.
Host parameters:
1. Number of detectable channels: 2 channels, 1 HFCT channel, 1 US channel
2. Sampling accuracy: 12bit
3, trigger mode: internal synchronization, external synchronization
HFCT parameters:
1, detection bandwidth: 0.5m-30mhz
2, transmission impedance: >5mV/mA(10MHz)
3, output impedance: 50 ω
4. Detection sensitivity: 5pC
5, measuring range: -20~80dB
6, the measurement error: ±1dB
7, resolution: 1dB
8, output interface: standard BNC
US parameters:
1, frequency range: 20khz-300khz
2, output impedance: 50 ω
3. Detection sensitivity: 0.1mV
4, measuring range: 0.1mV ~ 1V
5, output interface: standard BNC
Hardware parameters:
1, display: 4.3 "TFT true color LCD screen
2, resolution: 480×272
3, operation: film button
4, storage: SD card standard 4G card, the maximum support 32G
Interface: 3.5mm stereo headphone jack
Input port for DC-005 low voltage DC charger
Charging LED indicator light
RS232 debug port
Profile synchronous mouth
usb
internet access
SD card slot
CH1: SMA external HFCT transformer input port
US: SMA external HFCT transformer input port
6, the power supply
Internal power supply: Battery powered (16.8V lithium battery)
Normal working time: about 7 hours, full time about 3 hours
7, size: 235mm×133mm×48mm
8, weight: 0.85kg
9, the use of ambient temperature: -20℃ to 50℃
10, storage environment temperature: -40℃ ~ 70℃
11, humidity: 10%-90% (non-condensing)
12, altitude: ≤3000m