Welcome to visitWuhan Xinshengneng Technology Co., Ltd.
  • Withstand voltage test equipment

  • High voltage test equipment such as transformers and switches

  • Oil and gasification test equipment

  • Relay protection and secondary circuit test equipment

  • Live and online monitoring equipment

  • Electricity inspection power metering equipment

  • Insulation tool test equipment and battery

  • Others

  • High voltage integrated equipment series

  • SF6 gas test equipment series

  • Insulating appliance series

  • Marketing measurement test equipment series

  • Cable tester series

    XSN-TC-01 Cable fault tester

    Views:

    Product Introduction:

    Xsn-tc-01 cable fault tester adopts acoustic vibration sensor with special structure and special device with low noise for preamplification, which greatly improves the sensitivity of fixed point and path detection. In signal processing technology, digital display of the distance between the fault point and the sensor probe, greatly eliminate the blindness of fixed point. For the fault cable overhead in the cable trench, in the past fixed point, the vibration sound of the whole cable makes any fixed point instrument helpless, unable to determine the specific location of the sealing fault. Now, as long as the sensor probe of the instrument is in contact with the fault cable or nearby cable, the fault distance and direction can be accurately displayed, and the fault location can be quickly determined effortlessly. In addition, adaptive power-frequency cancellation theory and high-Q power-frequency notch technology should be used to greatly strengthen the suppression and anti-interference ability of 50Hz power-frequency signal in the strong power-frequency electric field environment, and reduce the fixed-point blind area. In the function of the instrument, the difficulty of fixed point caused by environmental noise is overcome effectively by using the technology of acoustic and electric synchronous receiving and displaying. In particular, the digital display of fault distance saves the operator's analysis and judgment of complex waveform and to a considerable extent replaces the function of the flash meter to measure the rough distance. For hundreds of meters long fault cable, it can be fixed without rough measurement, which is really efficient, fast and accurate. Using 16kHz amplitude modulation electromagnetic wave and amplitude detection technology for path detection and cable buried depth measurement, avoid the interference of TV line frequency to the fixed point meter when the original 16kHz constant signal source.

    Product features:

    1, wide range of use: used for measuring a variety of different sections, different media of various power cables, high-frequency coaxial cable, local telephone cable and more than two uniformly laid buried wire cable high and low resistance, short circuit, open circuit, broken line and high resistance leakage and high resistance flasover fault. It can also be used to measure the length of cable and the propagation speed of radio wave in cable.

    2, easy to carry: the host is powered by lithium battery, lightweight, easy to carry, convenient for field test and mine cable test;

    3, friendly man-machine interface: using a large screen 320×240 dot matrix Chinese graphic interface, high brightness graphics clear and beautiful, simple operation, strong anti-interference;

    4, safe and reliable: the use of new current sampler, a brand new sampling method, with simple wiring, waveform intuitive easy analysis, complete isolation from high voltage, the host, the operator is absolutely safe;

    5, high quality: all the key components are imported components, to ensure the accuracy of test results;

    6, beautiful appearance: the use of strong and wear resistance of the material, so that the overall texture of the instrument and longer service life;

    7, path meter, fixed point meter receiving sensitivity is high: the use of special production process, transmission distance increases, the instrument can still receive signals clearly;

    8, path meter, fixed point meter core components are imported components, reliable performance;

    9, path instrument, fixed point instrument using quartz crystal oscillator, high-speed signal processing chip for signal sampling and processing, to ensure accurate and reliable positioning accuracy;

    10, path instrument, fixed point instrument in severe interference conditions, the instrument can still ensure good performance, stable work;

    11, easy to carry: built-in rechargeable battery power, suitable for all kinds of occasions.

    Product names: cable fault tester, power cable fault tester, street lamp cable fault tester, cable fault pathfinder, cable fault finder, portable cable fault location system, cable fault flash tester, geographical cable fault tester, cable path meter, cable fault tester

    Test subjects:

    Cable communication cable and power transmission cable line maintenance important testing tools.

    Cable fault tester technical parameters:

    1, ambient temperature: -10℃ ~ 40℃

    2, measurement error: coarse measurement error ±1%

    3, the test distance: the longest 16km

    4, the shortest test distance (blind zone) : 1 ~ 3m

    5. Sampling rate: 25MHz

    6, power supply and power consumption: AC or dc power supply; AC 220V±10%, power consumption is not more than 10W; DC 6V/7AH, power consumption is less than 6W

    7, the machine pulse width and amplitude: 0.2μs, 100 ~ 120V; 2μs, 150 ~ 160V

    8, working mode: low voltage pulse, DC high voltage flash and impact high voltage flash method

    9, display resolution: V/50 meters, V for propagation speed m/μs

    10, display mode: 320×240 LCD LCD with backlight display

    11, quality: 6kg

    12, volume: 500×300×195mm3

    Technical parameters of path meter and fixed point meter:

    1. Tracing working mode: output - fixed frequency discontinuous square wave signal

    2, output power: Pomax≥100W

    3, output impedance: 1 Ω -∞

    4. Signal frequency: 16kHz

    5, signal amplitude: 15V-340V

    6, path meter transmitter power supply: AC220V± 10%

    7, rough measurement error: < 10%

    8, fixed point error: <±10cm

    9, electromagnetic channel gain: >110dB (300,000 times)

    10, electromagnetic channel receiver sensitivity: <5μV

    11. Burial depth detection: <3m

    Back To Top
    Copyright © Wuhan Xinshengneng Technology Co., Ltd. All Rights Reserved  鄂ICP备2020019985号-1   Web site productionsanjin.net