Product introduction:
Xsn-hzn1 intelligent transformer calibrator is used for error, impedance and admittance test of PT and CT. It meets the requirements of national JJG313-94 Verification Regulation of current transformer for Measurement and JJG314-94 verification Regulation of voltage transformer for Measurement.
Product features:
1, intelligent transformer calibrator adopts 320×240 dot matrix LIQUID crystal, large visual range, with long life backlight lighting, easy to use;
2, full Chinese operation interface, beautiful interface;
3, dial indicator, ratio difference, Angle difference using large font display, convenient user observation;
4, the intelligent transformer calibrator produced by the company fully meets the requirements of JJG314-1993 and JJG314-1994, automatic sampling;
5, automatic judgment polarity error, change ratio error;
6. The upper computer software has the open function of virtual instrument;
7. Completely solve the s-class measurement problem;
8, automatic switching range;
9, the use of advanced unique circuit and DSP technology perfect combination, completely remove the resistance and capacitance phase shift circuit instability problem;
10, power consumption: < 15VA(without micro printer); < 25VA(with micro printer);
11, harmonic suppression ratio: > 40dB;
12, size: 260×350×150mm
13, weight: 6kg
Product names: transformer calibrator, transformer current calibrator, automatic transformer calibrator, automatic current transformer calibrator, automatic voltage transformer tester, transformer field calibrator, current transformer field calibrator, voltage transformer field calibrator
Device Operating environment | The temperature:5℃~40℃ | Relative humidity:<80%(25℃) |
The altitude:<2500m | ||
Power frequency:50Hz±0.5Hz | The power supply voltage:220V±5V | |
Measuring range | In-phase component(%):0.0001~200.0 | The resolution:0.0001 |
Quadrature component(分):0.001~700.0 | The resolution:0.001 | |
impedance(Ω):0.0001~20.0 | The resolution:0.0001 | |
admittance(ms):0.0001~20.0 | The resolution:0.0001 | |
The basic error | In-phase component | ΔX=±(X×2%+Y×2%)±Dx(Level 1 is available) |
Quadrature component | ΔY=±(X×2%+Y×2%)±Dy(Level 1 is available) | |
"X"、"Y"——Instrument display value | ||
"Dx,Dy"——Quantization error of instrument | ||
Dx=2,Dy=5 | ||
Dial indicator | 2level(Level 1 is available) | |
The scope of work | current | (1%~149%)In (In =5A) |
(5%~149%)In (In =1A) | ||
voltage | (5%~149%)Un (Un =100V,150V,100V/)√3 | |
(5%~149%)Un (Un =100V/3) | ||
The workload |
current | TO对TX<0.12Ω cosΦ=1 |
voltage | a对x<0.25VA (100V) | |
Polarity error indication | When the operating current (voltage) reaches more than 5% of the rated current (voltage) and the error exceeds 180%, there should be polarity indication. | |
If it is more than 10% of the rated operating current (voltage) and still does not show the due polarity indication, it indicates that there is a fault, please do not increase the current (voltage), so as not to burn the instrument. | ||
Change ratio error indication | When the operating current (voltage) reaches more than 5% of the rated current (voltage), the error is more than 30% and less than 180%, there should be a ratio error indication. | |
Insulation and pressure test and specification | Terminal TX() The terminal is connected | |
The power socket can withstand 1.5kV and 1min of pressure to the shell |