Product Introduction:
XSN-CT901 high and low voltage CT ratio variable tester can measure the high voltage primary current and low voltage secondary current of the high voltage metering device of 35KV and below system without disconnecting wires and continuous electricity on site, and calculate the variable ratio and ratio error. The high-voltage clamp meter (hereinafter referred to as the clamp meter) is installed at the end of the high-voltage insulation rod to collect current signals. When working, wireless transmission is adopted to send the collection results to the handheld terminal, which directly collects the secondary current of the low-voltage current transformer. Handheld terminals will be according to the received data, real-time computing, current transformer primary/secondary current, variable than electricity parameters, such as at a glance, clamp table adopts the design of clamp type connection insulation rod jog, gently pull can clamp enter and exit a conductor, smoked pull type high voltage insulation lever elongation can be up to 5 meters, ensure the safety of the operation process.
Product features:
1. Measure primary and secondary current and electrorheological ratio of high and low voltage CT without power failure on site;
2, the primary current signal adopts wireless transmission, to ensure the safety of operation;
3, a clamp meter and high voltage insulation rod connected, can be very convenient to measure the current in the air;
4, the tester adopts 320*240 high dot matrix true color liquid crystal, the interface is clear and intuitive;
5, can measure CT ratio difference, Angle difference, easy to check the FIRST and second CT phase difference, phase sequence;
6, the host and clamp head are using high-speed DSP MCU;
7, high voltage current closed clamp head gently push, gently pull can clamp into, out of a wire, convenient and safe operation;
8, high voltage can be measured within 32 times of harmonic;
9, can store 2000 pieces of field test data.
Technical parameters:
1. Wireless transmission distance: the reliable transmission distance is more than 200m in the case of no obstacles
2, current range: clamp type current sensor once: 500A
3, current sensor secondary: 5A
4, variable ratio measurement range: 1-5000
5, measurement accuracy: 1%
6, pressure: 70000V/1 minute
7, weight: host 0.5kg, a clamp table 0.5kg, two clamp table 0.15kg
8, high voltage insulation rod for telescopic structure, the maximum elongation of 4 meters