■ Technical parameters
▲ Switch circuit resistance test function
- Input power supply: AC220V±10%, 50HZ±1HZ
- Output current: ≥DC100A Current adjustment range: DC50-100A (DC200A optional)
- Test duration: 15s-180s is optional
- Measuring resistance range: 0-3000.00μ
- Test accuracy: 0.2% RDG ±1μ
▲ Switch action voltage test function
- Input power supply: AC220V±10%, 50HZ±1HZ
- Output voltage: DC0-300V adjustable
- Maximum current: 20A
- Voltage range: 1V, 3V, 5V, 10V
- Test accuracy: 0.5% RDG ±1V
- Can be fully automatic low voltage one button operation, and automatic record printing; Manual low voltage test is available
▲ Switch mechanical characteristics test function
- Input power supply: AC220V±10%, 50HZ±1HZ
- Output voltage: DC0-300V adjustable
- Maximum current: 25A
- Trigger mode: internal trigger, external trigger (closing two split two), fracture trigger and sensor trigger (meet the switch test on the column) four
- Sensor: acceleration sensor, rotation sensor, linear sensor and auxiliary contact speed sensor
- Time measurement range: 0-64000.0ms (suitable for all kinds of high and low voltage switches and isolation switches test)
- Test accuracy: 0.1% RDG ±0.1ms
- Stroke test range: 0-1000.0mm
- Test accuracy: 0.5% RDG ±1mm
- Speed test range: 0-20.00m/s
- Test accuracy: 0.5% RDG ± 0.1m /s
- U disk storage, PC management software, print out standard report format