Reactive power compensation capacitor is an important equipment to satisfy reactive power balance in power system. A large number of reactive power compensation devices are put into the distribution network to balance the active power and reactive power in real time. Reactive power compensation device should meet the requirements of automatic tracking and real-time compensation, so it is inevitable to frequently cast and cut reactive power compensation capacitor banks. The switching and switching operation of the capacitor bank will produce overcurrent and overvoltage impact, causing damage to the capacitor. In order to ensure the reliability of the equipment, it is necessary to detect the capacitor defects early and avoid the expansion of the fault regularly. Capacitance inductance tester is specially used for measuring capacitors and reactors of reactive power compensation system. The instrument adopts advanced measuring principle and four-terminal measuring technology to measure group shunt capacitors and various reactors.
The main features
- The instrument can be connected in one time to complete the capacitor measurement of the three-phase capacitor bank without removing the wire.
- The instrument also has inductance, resistance and current measurement functions.
- The instrument has two power supply modes: external AC220V and built-in lithium battery to meet various application scenarios.
- The instrument has perfect over current protection function.
- 8.0 inch touch screen, easy to operate.
- Built-in large capacity of non-volatile memory, can store 200 groups of data.
- Built-in high speed micro thermal printer, can print measurement data.
- Built-in high precision clock, real-time display time.
- With U disk storage function.
- Built-in large capacity lithium battery, one charge can be switched on for more than 8 hours.
Technical parameters
Capacitance range |
0.1uF~6800uF |
Capacitance accuracy |
Reading 1%+0.01uF |
Inductance range |
100uH~20H |
Accuracy of inductance |
Reading3%+0.01mH |
Current range |
5mA~20A |
Accuracy of current |
Reading3%+0.1mA |
The resistance range |
50mΩ~20kΩ |
Precision of resistance |
Reading3%+1mΩ |
- Test voltage: AC25V±10%, 50Hz AC1.25V±10%,50Hz 25VA
- Resolution: 4 significant digits
- Host size: 405mm×330mm×180mm
- Main weight: 8.5kg
Using parameter
- Ambient temperature: -10 ° C to +50 ° C
- Ambient humidity: ≤85℅RH, no condensation
- Power supply: AC220V ±10% or DC29.4V