Product Name: Automatic Capacitance Current Tester (Neutral Point Capacitance Method)
Product specifications: XSN-DR-Z1
Product introduction: XSN-DR-Z1 automatic capacitance current tester, adopts the neutral point capacitance method to measure the distribution network capacitance current. The tester adopts a large-screen LCD display and a Chinese menu. After safety measures are taken, the instrument parameters are set in advance There is no need to touch the operating instrument, making this work safe, simple and fast, and the test results are accurate, stable and reliable, and are not affected by other operating conditions, especially when the system is unbalanced.
Features:
1. It adopts large-screen LCD display and Chinese menu. After safety measures are taken, there is no need to touch and operate the instrument after setting the instrument parameters in advance;
2. The test results are accurate, stable and reliable, and are not affected by other operating conditions, especially when the system is unbalanced;
Product nicknames: automatic capacitance current tester, microcomputer capacitance current tester, distribution network capacitance current tester, distribution network capacitance current tester, distribution network capacitance current test system, automatic capacitance current tester, distribution network Power grid microcomputer capacitance current tester, capacitance leakage current tester.
Test object:
Aiming at the problems existing in measuring the capacitive current of the distribution network.
technical parameter:
1. Measuring range: total capacitance to ground ≤120μF (three phases to ground)
Capacitance current ≤1000A (66kV system)
Capacitance current ≤700A (35kV system)
Capacitance current ≤200A (10kV system)
Capacitance current ≤100A (6kV system)
2. Capacitance measurement accuracy: 0.5μF~1μF ±10%±5 words
1μF~90μF ±5%
90μF~120μF ±10%
Capacitance current <10A ±10%
Capacitance current 10A-500A ±5%
Capacitance current 500A-1000A ±10%
3. Ambient temperature: -10~50℃
4. Relative humidity: ≤90%
5. Power supply: AC220V±10%, 50Hz ±1%
6. Dimensions: 310×300×170mm³
7. Instrument weight: 10KG