Welcome to visitWuhan Xinshengneng Technology Co., Ltd.
  • Withstand voltage test equipment

  • High voltage test equipment such as transformers and switches

  • Oil and gasification test equipment

  • Relay protection and secondary circuit test equipment

  • Live and online monitoring equipment

  • Electricity inspection power metering equipment

  • Insulation tool test equipment and battery

  • Others

  • High voltage integrated equipment series

  • SF6 gas test equipment series

  • Insulating appliance series

  • Marketing measurement test equipment series

  • Series resonance

    XSN (XZ) -135kVA/54kV frequency conversion cable series resonance

    Views:

    ● Product Overview

    Product Name: 35kV (135kVA/54kV) frequency conversion cable series resonance

    Product specifications: XSN (XZ) -135KVA /54kV(frequency conversion)

    Applicable to test products: cable, switch, transformer

    Range of tested products: 35kV/300mm2 cable 1km,10kV/300mm2 cable 3km,10kV switch transformer

    Product functions and functions:

    1. Help customers to carry out preventive ac pressure test and handover AC pressure test of various tested products;

    2. Ac voltage withstand test of cross-linked rubber and plastic power cables, power transformer, GIS, transformer, insulator, generator, switch and other tested products' insulation ability to withstand various overvoltages and capacitive loads.

    Product name:

    Series resonance withstand voltage test complete set, AC withstand voltage test complete set, resonance boost device for inspection, series resonance withstand voltage tester.

    Test subjects:

    1, 35kV/300mm2 cable 1km AC voltage test, capacitance ≤ 0.1945UF, test frequency 30-300Hz, test voltage 52kV, test time;

    2, 10kV/300mm2 cable 3km AC voltage test, capacitance ≤1.126uF, test frequency 30-300Hz, test voltage 22kV, test time;

    3. Ac voltage withstand test of 10kV switch and transformer, test frequency 30-300Hz, test voltage does not exceed 42kV, test time.

    ● Technical parameters

    1, product core parameters: rated capacity: 135kVA;

    Input power: single-phase 220 or three-phase 380V voltage, frequency is 50Hz;

    Rated voltage: 27kV; 54 kv;

    Rated current: 5A; 2.5 A.

    Operating frequency: 30-300Hz;

    Device output waveform: sine wave

    Waveform distortion rate: output voltage waveform distortion rate ≤1%;

    Working time: continuous 60min under rated load; Overvoltage 1.1 times 1 minute;

    Temperature rise: temperature rise ≤65K after 60min continuous operation under rated load;

    Quality factor: Q≥30(f=45Hz);

    Protection function: over current, over voltage and flashover protection (see frequency conversion power supply);

    Measurement accuracy: system effective value 1.5 level;

    2, excitation transformer JLB-7.5kVA/1.5/3kV/0.4kV 1

    Rated capacity: 7.5kVA;

    Input voltage: 0-400V, single phase;

    Output voltage: 1.5/3kV

    Structure: dry type;

    Weight: about 48kg;

    3, frequency conversion power BP - 7.5 kW / 220/380 v 1

    Rated output capacity: 7.5kW

    Power supply: 220/380±10%V (single/three phase), power frequency

    Output voltage: 0 -- 400V, single phase,

    Rated input current: 18.75A

    Rated output current: 18.75A

    Voltage resolution: 0.01kV

    Voltage measurement accuracy: 1.5%

    Frequency adjustment range: 30-300Hz

    Frequency adjustment resolution: ≤0.1Hz

    Frequency stability: 0.1%

    Operating time: continuous 60min at rated capacity

    Maximum temperature of components ≤65K during continuous operation at rated capacity for 60min;

    Noise level: ≤50dB

    4, high voltage reactor DK (G) -33.75kVA/27kV 4 sections

    Rated capacity: 33.75kVA;

    Rated voltage: 27kV;

    Rated current: 1.25A;

    Inductance: 100H/ single section;

    Quality factor: Q≥30 (f=45Hz);

    Structure: dry type;

    Weight: about 40kg;

    5. One set of capacitor divider FY-60KV /1500pF

    Rated voltage: 60kV;

    High voltage capacity: 1500pF;

    Dielectric loss: TG σ≤0.5%;

    Partial pressure ratio: 1000:1

    Measurement accuracy: effective value 1.5 level;

    Weight: about 6kg;

    Back To Top